Описывается система обнаружения пожара и присутствия газа и система автоматического останова (F&G/ESD).

The Emergency Shutdown logics shall be activated only through two yellow emergency push-buttons, one in Radio room near the F&G/ESD Cabinet and the other in Mess Room near the evacuation door.
The ESD system is based on relays that perform the power supply drop for the following subsystem:

Fire Water emergency pump battery;
Emergency service UPS;
Telecom UPS;
Radio Solas UPS;
Navaid UPS;
PAGA A UPS;
PAGA B UPS;
PABX UPS;
VSAT (Agip) UPS;
VSAT (Driller) UPS.

Moreover the ESD system unlocks the evacuation door 1-4 recreation area.
The ESD System shall be bypassed using the key selector mounted in the internal side of the front panel.

power supply drop - ? отключение или подключение?
Коль речь идет об аккумуляторе аварийного насоса пожаротушения, о радиосистеме Solas, то вроде, надо подавать питание. Но почему тогда это система автоматического ОСТАНОВА?

 Bigor

link 29.01.2007 19:05 
написано в оригинале коряво, поэтому объясню, о чем здесь речь.
все цепи системы аварийного останова выполнены по так называемой "отказобезопасной" схеме, т.е. в нормальном режиме на обмотки "relays that perform the power supply drop" подается напряжение,
и ваши UPS и отключены Fire Water emergency pump battery. В аварийном режиме цепи системы аварийного останова обесточиваются (power supply drop), что приводит к отпусканию упмянутых реле, контакты которых включают перечисленные системы.

 