Subject: open door operation bel.usg.
Locally opening/closing 750-13,800 V disconnecting devices (breakers, disconnect switches) at the MCC, switch rack, or distribution switchgear level with the enclosure fully secured.
Racking in/out 380-13,800 V motor starters (contactors or circuit breakers) or distribution circuit breakers as designed.
This includes removing/inserting 380 V MCC "cans" on energized bus.
Manual tripping of circuit breakers utilized at 750 to 15,000 V with enclosure intact.
Racking in/out 2,400-13,800 V Potential Transformers (PTs) and Control Power Transformer (CPT) primary fuses.
Removing/installing energized 380 volt PT and Ground Detection System pull a part fuse blocks (not exposed).
Locally opening/closing 15-230 kV non-load break air disconnect switches whose load has been removed, 15-230 kV circuit breakers, and 15-230 kV circuit switchgears.
Switching circuit breakers designed for **open door operation** (Ex:
Westinghouse DS Breakers)
Routine switching:
Generic or Specific Switching Operating Procedure or SWP
Non-routine switching:
Specific Operating Procedure or SWP
Class A-1 Energized Electrical Work
Class A-1 energized electrical work has the most restrictive requirements, and can only be performed after a Pre-Task Analysis and with Two Electrical Skilled Persons present (see table below for complete requirements).
If you are asked to issue a Safe Work Permit for Class A-1 energized electrical work, please make sure you engage your facility electrical representative.

 InnArt

link 30.11.2015 5:51 
М.б."... предназначены для работы/эксплуатации на открытых площадках"?

 Oleg Sollogub

link 30.11.2015 6:22 
Похоже, тут речь об открытых дверцах оборудованя, скорее всего - шкафа, где это все установлено

 