Subject: in which no loading/unloading occurs. gen. Документ о промышленных системах охлажденияStep control solution for compressor capacity can be achieved by using a step controller EKC 331 À. EKC 331 is a four-step controller with up to four relay outputs. It controls the loading/unloading of the compressors/pistons or the electric motor of the compressor according to the suction pressure signal from the pressure transmitter AKS 33 Á or AKS 32R. Based on a neutral zone control, EKC 331 can control a pack system with up to four equally sized compressor steps or alternatively two capacity controlled compressors (each having one unload valve). EKC 331T version can accept a signal from a PT 1000 temperature sensor, which may be necessary for secondary systems. Neutral Zone Control A neutral zone is set around the reference value, ***in which no loading/unloading occurs. Касательно последнего предложения: сомневаюсь к чему относится "in which" - к neutral zone или к reference value. И буду благодарна за хотя бы прибл. перевод этого предложения. Спасибо!
|